PV túlfeszültség levezető, T2
Standards | IEC-61643-1 | ||
Max. continuous operating voltage (DC) | Uc | V | 1000 |
Nominal discharge current (8/20) | In | kA | 20 per pole |
Max. discharge current (8/20) | Imax | kA | 40 per pole |
Protection level | U p |
kV | < 4,0 |
Follow current | I f |
ARMS | NO |
Response time | tA | ns | < 25 |
Residual current at U c |
I PE |
mA | < 1,5 |
Thermal protection | YES | ||
Terminal screw torque | Nm | max. 4,5 | |
Back-up fuse gL (if mains > 125 A) | A | 125 | |
Short-circuit withstand current (50 Hz) | kA | 25 | |
Temperature range | º C | -40 … +80 | |
Terminal cross section solid | mm2 | 35 | |
Terminal cross section stranded | 25 | ||
Mounting | 35 mm wide mounting rail in accordance with EN 60715 | ||
Degree of protection | IP 20 | ||
Housing material | thermoplastic; extinguishing degree UL 94 V-0 | ||
Dimensions DIN 43880 | 3TE | ||
Weight per unit | kg | 0,403 |